Search
Close this search box.

Overfill Prevention Controller EUS-2

Overfill Prevention Controller EUS-2

exkl. 19% MwSt. zzgl. Versandkosten

auf Anfrageliste setzten

Beschrijving

  • Monitors bottom loading of liquid fuels in the petrochemical industry:
    • Overfill prevention
    • Grounding control
    • Vapour recovery hose
  • Immediate interruption of the filling in the case of detecting a factual overfilling of a tank compartment or if a proper electrostatic grounding is not detected
  • Automatic recognition of the connected tank truck according to European standard EN 13922 and American standard API RP 1004
  • Explosion protection for worldwide use according to IECEx and the European ATEX Directive 2014/34/EU and Indian CCOE/PESO approval
  • Tested in accordance with EN 61508:2010 (SIL2 – Safety Integrity Level 2)
  • Complete compatibility – independent from the sensor manufacturer – with all 5-wire, 2-wire or other sensors according to EN 13922

Contact Person

TIMM Support Chen

Do you have questions about the product?

Do you have questions about the product or the TIMM-Onlineshop? Please contact me!

Yi Chen
Sales Engineer Gas Ex

write an E-Mail
+49 (0) 40 248 35 63 – 36

Benefits

  • Plain text messages display in mother tongue of the operator
  • Opening of the housing during operation in hazardous areas is allowed
  • Intuitively operation of configuration menu via innovative joystick navigation
  • Serial data interface (Ex ib) for connection with the TExi data bus (intrinsically safe data bus by Timm Elektronik)

Technical Specifications

Type of Protection:According to ATEX-standards 2014/34/EU:
Ex II 2 [1] G Ex eb ib q [ia Ga] IIB T4 GB
EC Type Examination:TÜV 13 ATEX 132121
IECEx Certificate:IECEx TUN 16.0004
SIl 2 Certificate:EN 61508:2010 (SIL 2)
Power Supply:230 V AC ± 10 %, 50-60 Hz, ca. 25 VA
type of protection “higher safety“ Ex eb
Output Circuits:
Contact Circuits (K1 to K4)
Max.: 250 V AC, 3 A, 100 VA
type of protection “increased safety“ Ex eb
Output Circuits:
Electronical Outputs (E1, E2)
Max. values of the certified intrinsic circuits:
Ui = 15 V; Ii = 20 mA, Po = 300 mW
Type of protection “intrinsic safety“ Ex ib NAMUR compatible
Serial Data Interface:Type of protection “intrinsic safety“ Ex ib, TExi data bus
Level Sensor Circuits:Type of protection “intrinsic safety“ Ex ia
Truck Connector Cable:PUR-special cable, blue, single shielding 10x 1 mm²
Truck Connector Plug:Standard: 10-pole (according to EU-standard and API thermistor)
Option: 7-pole (according to API standard “optical“)
Protection of Enclosure:IP67
Operation Temperature:– 40 °C up to + 60 °C
Dimensions (W x L x H):ca. 220 mm x 360 mm x 120 mm
Weight:
ca. 10 kg

Downloads