Type of Protection: |
According to ATEX-standards 2014/34/EU: Ex II 2 [1] G Ex eb ib q [ia Ga] IIB T4 GB |
EC Type Examination: |
TÜV 13 ATEX 132121 |
IECEx Certificate: |
IECEx TUN 16.0004 |
SIl 2 Certificate: |
EN 61508:2010 (SIL 2) |
Power Supply: |
230 V AC ± 10 %, 50-60 Hz, ca. 25 VA type of protection “higher safety“ Ex eb |
Output Circuits: Contact Circuits (K1 to K4) |
Max.: 250 V AC, 3 A, 100 VA type of protection “increased safety“ Ex eb |
Output Circuits: Electronical Outputs (E1, E2) |
Max. values of the certified intrinsic circuits: Ui = 15 V; Ii = 20 mA, Po = 300 mW Type of protection “intrinsic safety“ Ex ib NAMUR compatible |
Serial Data Interface: |
Type of protection “intrinsic safety“ Ex ib, TExi data bus |
Level Sensor Circuits: |
Type of protection “intrinsic safety“ Ex ia |
Truck Connector Cable: |
PUR-special cable, blue, single shielding 10x 1 mm² |
Truck Connector Plug: |
Standard: 10-pole (according to EU-standard and API thermistor) Option: 7-pole (according to API standard “optical“) |
Protection of Enclosure: |
IP67 |
Operation Temperature: |
– 40 °C up to + 60 °C |
Dimensions (W x L x H): |
ca. 220 mm x 360 mm x 120 mm |
Weight:
|