Type of Protection: |
According to TR-CU 012/2011 regulation:
1Ex e q [ib] IIC T4 Gb X for zone 1
Ex t [ibD] IIIC T80°C Db X for zone 21 |
Certificate of Conformity No.: |
ЕАЭС RU С-DE.АД07.В.04414-22 |
Power Supply: |
230 V AC ± 10 %, 50 Hz, ca. 10 VA
type of protection “increased safety“ Ex e |
Measuring Circuit: |
Max. Uo = 6,7 V; Io = 68 mA; Po = 114 mW
Max. 50 m (ex related specification, functional limitations must be observed)
Type of protection Ex ib / ibD Only for connection of the grounding cable
The measuring circuit is grounded |
Contact Release Output: |
Switching power max 250 VAC 3 A 100 VA
Type of protection “increased safety“ Ex e
2 voltage free closer, internal monitored |
Auxiliary Output: |
Switching power max. 250 VAC 3 A 100 VA
Type of protection “increased safety“ Ex e
voltage free changeover contact, not monitored |
Electronic Release Output: |
Max. Ui = 20 V Ii = 20 mA Pi = 400 mW
Inner capacitances Ci negligibly small
Inner inductances Li negligibly small
Type of protection “intrinsic safety“ Ex ib
1 NAMUR-compatible transistor output
Internal resistance: 1 kΩ or 11 kΩ
Modulation: 10 Hz, duty factor 1:1 |
Protection of Enclosure: |
IP65 |
Operation Temperature: |
– 55 °C up to + 50°C |
Dimensions (W x L x H): |
305 mm x 440 mm x 185 mm |
Weight: |
approx. 12 kg |